Normal circuit breakers or fuses are not recommended in place of surge protector. The reasons are as follows:
I. Problems with common Ordinary Circuit Breakers
Slow response: Normal circuit breakers typically move in milliseconds, while surge events last extremely short (nanoseconds to microsecond). This delay may cause the surge protector to fail before it can work and provide effective protection.
Can't withstand multiple shocks: Normal circuit breakers are designed to be overloaded or short-circuit protected, rather than frequent surge events. Multiple surges can cause them to fail prematurely, increasing maintenance costs and system downtime.
Insufficient interrupting capacity: Under the action of high energy surges, normal circuit circuit breakers not have sufficient the interrupting capacity to effectively cut fault currents, increasing the risk of equipment damage.
Risk of misaction: The short-term high-amplitude characteristic of surge current may cause the electromagnetic tripping device of a common circuit breakers to fail, causing the surge protector to lose its lightning protection function.
Residual voltage problem: Ordinary circuit breakers have internal inductance that generate high residual voltage when surge protector are activated. This can affect protection.
II. Fuze issue
Slow response to degraded short circuits: Fuses are slow to respond to "degraded short circuits" (small current continuous conduction of small currents) common to surge protectors, and can pose a fire risks due to excessive fuse melting time.
Failure to distinguish between surge current and fault current: Fuses cannot distinguish between surge current and fault current and may occur during surge discharge, causing the surge protector to lose its protective function.
Voltage limitation: In general, the rated maximum working voltage of a low-voltage fuse is limited, and the surge protectors may protect several times the maximum working voltage of the fuse. Even with a fuse, when the surge is strong enough, the fuse can simply explode and fail to provide protection.
III. Advantages of surge backup protection
Precise protection: Surge backup protection device is specially designed for surge protection device. They can accurately distinguish surge currents from fault currents. When surge protectors fails due to continuous short circuit caused by ageing or overvoltage, the surge backup protector can be quickly interrupted. During normal surge discharge, the surge protector can still conduct electricity to ensure that the surge protector as a lightning protection device.
Matching action characteristics: Surge backup protection device adopts the double standard trigger mechanism, realizes the accurate protection by the comprehensive judgment to current amplitude and duration. It can withstand short bursts of high current (surge current) from a surge protector, and when the current duration exceeds a set threshold, it is identified as a surge protector failure and quickly interrupted.
Standard requirements: the design of surge backup protection devices complies with relevant standard requirements.